Industrial electrical, automation, robotics & mechanical solutions for Australian manufacturers(03) 9761 8500 · [email protected]
Electrical · Automation · Food & Beverage

New Pakenham food facility electrical fit-out

Complete electrical infrastructure for a new food-manufacturing facility — distribution boards, machine supplies and process controls, delivered to the build program.

A food manufacturer fitted out a new facility at Pakenham. Mobile Automation delivered the electrical infrastructure — distribution, machine supplies and process controls — to the construction program.

Stainless droppers instead of surface runs

The process rooms are built from fridge panel, so cabling was kept off the internal surfaces.

  • Tray and basket tray carried above the panel roof and off the H beams
  • Allthread, beam clamps and unistrut used for support, with every ceiling penetration drilled and sealed
  • Outlets and data points hung on stainless wire droppers, heat shrunk over the flex and jointed at beam level
  • Stainless brackets and food-grade ties throughout

Mains proven before the boards went up

Pre-run mains were tested for polarity before each board was mounted.

  • 400 mm² and parallel 240 mm² aluminium conductors dressed in
  • Aluminium-to-copper joints crimped, lugged and heat shrunk
  • New busbars and a main switch tied to the existing bars
  • Boards labelled, neutral tails ferruled, legends and schedules written
  • Each board commissioned circuit by circuit

Power, data and fibre on separate paths

Power circuits, category 6 data and optical fibre ran on their own trays and droppers.

  • Data velcroed rather than tied so runs can move when points change
  • A separate enclosure built up for the fibre unit — mounting plate, ducting and DIN rail
  • Power and control wiring run into the fibre enclosure
  • Every data run terminated, tested and the results documented

The results

  • Machine supplies dropped into control cabinets on unistrut and jack chain
  • Every drive configured on site, parameters entered and direction of rotation proven
  • A pump drive pulling 16 to 18 amps on a 10 amp single-phase supply measured, traced to a failed contactor and repaired
  • Contactor and cabling replaced, maximum frequency held at 40 hertz to bring current back to 10 amps
  • Full 50 hertz restored once the socket was upgraded to 20 amps

Explore food & beverage support

Call (03) 9761 8500Request a Quote